The closed cooling system KS 88.0100 is made for cooling of HF-generators
and similar equipment where a clean cooling
water and controlled temperature is required.
Technical data: The unit is built on a welded construction
and consists of.
Pump type NMD 20/140B, with a capacity of 16/80
min. at 5,3/3, 5 bar, motor 1,1 kW 2900 r/m.
Tank of stainless steel containing 30 liters.
Heat exchanger, type Ultra Flex UFX-6 C with 12
cooling plates of stainless steel.
Thermostat, type AVTA 20, adjustable between 25-65
degrees C.
All components having contact with water are made of non rusting material
such as copper, brass and stainless steel.
Weight: app. 100 kg.
| 1. Tank
2. Pump 3. Thermostat 4. Motor protector 5. Heat exchanger |